Signal Monitoring and Alerts

Overview​

Alerts let you check when signal conditions become active and recover. You can configure multiple conditions per signal. Distinguish the Monitor setting for the value list, the setting that enables alerts, and triggers that start/stop log saving.

PurposeSettings / screen to use
Check the latest valueValues / Monitor in Display Settings
Check activation/recovery of value conditionsAlert in Signal Setting, Alert History
Use a condition to start/stop log recordingStart/Stop Signal Trigger in Trigger Window
Find occurrences in a saved logSignal Analysis in Analyze Window

Configuring Alert Conditions​

  1. Stop monitoring and open Edit for the target signal in Signal Catalog.
  2. Select the Alert tab. For a derived signal, also use Alert in its editing screen.
  3. Add a condition with + Add and set its name.
  4. To also use a condition that supports real-time monitoring while monitoring, select “Monitor + Analysis” as its use. “Analysis only” applies to analysis of recorded logs. State transition is analysis-only.
  5. Turn on “Enable this condition.”
  6. Select the required condition from the options available for the signal type.
  7. Configure the supported thresholds, recovery conditions, notification delay, and notification sound if needed. State transition has no duration or recovery conditions.
  8. Check the condition summary and enabled state, then confirm with OK.
  9. For Monitor + Analysis conditions, start monitoring with the intended Set and check Values and Alert History. For analysis-only conditions, analyze a log in Signal Analysis and check the results.

Alert Tab Reference​

Figure 1 shows condition CH1 RPM High monitoring Simulated_RPM_demo in FanDemo. Its use is Monitor + Analysis and the condition is on. Upper limit under Range limits is 2200 rpm, Recovery margin is 100 rpm, and Notify is Immediately.

Alert settings with CH1 RPM High Monitor + Analysis and enabled state, Simulated_RPM_demo upper limit 2200 rpm, recovery margin 100 rpm, and Immediately outlined in red

Figure 1. Upper-limit condition for actual rotational speed.

ItemDescription
Condition list / Alert conditionsCheck registered conditions and the enabled count. Select a condition to edit.
Condition nameSet a name to distinguish multiple conditions.
Monitor + Analysis / Analysis onlySpecify whether the condition is used in real-time monitoring as well, or only in analysis.
Enable this conditionEnable or disable the selected condition.
Range limitsUse lower/upper-limit conditions. Enable the required side. The upper-limit condition becomes true at or above the configured value.
Equals / Does not equalTest whether values match or differ.
Is one of / Is none ofTest whether a value matches any specified state or none of them.
Text matches / Text does not matchTest whether strings match or differ.
Invalid BCDDetect values invalid as BCD.
State transitionAn analysis-only event detecting the instant of a state transition. Not used for monitoring notifications; no duration or recovery conditions are configured.
No receptionTest whether the target signal has not been received for the specified time.
Condition detailsCheck the target value, comparison method, and condition summary.
Recovery marginA margin to prevent repeated activation/recovery near a threshold.
NotifySpecify Immediately or After duration.
Sound / PreviewConfigure a notification sound and check it with Preview.
+ Add / Delete / UndoAdd/delete conditions or undo edits.

Available conditions and fields depend on the signal type. Do not confuse numeric physical values, Logical states, and strings; check the comparison target in Condition details. For derived signals, the item that checks for missing input updates is shown as No result update.

Upper-Limit Example​

The condition in Figure 1 becomes true when actual rotational speed reaches 2200 rpm or higher. With Recovery margin set to 100 rpm, recovery occurs when the value falls below 2100 rpm. Notify is Immediately, so activation is reported immediately.

For After duration, set how long the condition must remain true before notification. Choose according to whether you need to detect momentary changes or only abnormalities lasting a specified time.

Alert History Reference​

Click Alert History at the upper right of Signal Window.

Figure 2 shows history from actual monitoring with the condition in Figure 1 enabled. Timestamp and Start Value record activation; Recovery Time and Recovery Value record recovery.

Alert History for CH1 RPM High with activation time/value and recovery time/value outlined in red

Figure 2. Alert History recording activation and recovery.

State in Figure 2 is Recovered. Condition CH1 RPM High for Simulated_RPM_demo became active at +000:00:01.264.351 with 2200 rpm, and recovered at +000:00:31.480.286 with 2092 rpm.

ItemDescription
StateCheck the alert activation/recovery state.
Signal / RuleCheck the target signal and condition.
Timestamp / Start ValueCheck activation time and the value at that time.
Recovery Time / Recovery ValueCheck recovery time and the value at that time. Scroll horizontally to see later columns.
Signal Type / Rule Type / ConditionCheck signal/condition types and the evaluation condition. Figure 2 shows Native, Monitoring, and >= 2200.
Export CSVExport history to CSV. This has a different purpose from signal analysis CSV files and communication logs.
Open in Signal AnalysisExamine the selected history in Signal Analysis when available.
ClearClear recovered history entries. Active alerts remain.
CloseClose the history screen.

Stop monitoring and select the same history row to enable Open in Signal Analysis as shown in Figure 3.

Four buttons at the bottom after stopping and selecting a history row, with the enabled Open in Signal Analysis button outlined in red

Figure 3. Controls for opening selected history in Signal Analysis.

To examine a history occurrence in analysis, stop monitoring and analysis, then double-click the history row or select it and click “Open in Signal Analysis.” Data at the activation time must still be in the target channel's monitoring buffer. For derived signals, channels required for inputs are included too.

For checking detection rows, waveforms, and Values after opening, see Checking Alert Occurrences.

Alerts Versus Signal Trigger​

Enabling an alert alone does not make it a condition for starting or stopping log recording. To control log saving using a signal condition, configure the target signal, threshold, comparison direction, and other settings in Start Signal Trigger/Stop Signal Trigger in Trigger Window. Also check the trigger mode and Save Log File.

Restrictions apply to signals selectable for Signal Trigger; derived signals cannot be selected. Check availability and the reason shown in the selection screen. Also see the existing trigger features.

Saving and Reusing Conditions​

After editing conditions, use Save in the Catalog to save them to MPXSIG. To retain history, use Export CSV in Alert History. Saving conditions and saving recorded history are separate operations.

For saved-log analysis, result output, and use in transmission settings, see the respective instructions.